Spring Loaded

Actaris / Schlumberger Spring Loaded Service Regulators are simple direct acting regulators designed for accuracy, safety and dependability. Spring loaded service regulators are used primarily for final stage lower outlet pressure applications (Inches W.C. to 2 or 5 psig). Typical applications include residential and low outlet pressure commercial and industrial gas supply, and all types of gas-fired equipment including furnaces, boilers, dryers, ovens, heaters, etc.  Spring loaded regulators provide extremely fast response to changing downstream flow conditions. Unique features of Actaris / Schlumberger spring loaded service regulators include:

  • Controlled Boost
    All regulators are equipped with boosting devices (B42: raised lip on valve seat, all others: adjustable loading ring) to offset pressure droop at high flows caused by spring and diaphragm effect.
  • Controlled Breather Opening
    All regulators are equipped with a soft seat vent valve to ensure proper breathing and stability under all conditions
  • High Capacity Internal Relief
    All spring loaded regulars are equipped with internal relief as standard. Relief flow paths are as large as practical to provide the least resistance to venting gas in the event of an over pressure situation, thus minimizing pressure build-up
Spring Loaded Principle of Operation

Inlet pressure is reduced to a lower outlet pressure by restricting flow through an orifice to match a fluctuating downstream demand.

 

image11.gif (20052 bytes)
  1. As downstream demand increases, outlet pressure drops slightly, and the diaphragm moves downward. The valve seat moves farther away from the orifice face to allow flow to increase to match the increased demand.
  2. As downstream demand decreases, outlet pressure increases slightly, moving the diaphragm upward. The valve seat moves closer to the orifice face to restrict flow to match the decreased demand.
  3. When demand is shut off, outlet pressure continues to rise, moving the diaphragm up farther. The valve seat is driven into the orifice face, shutting off the flow of gas bubble-tight (lockup).

 

image12.jpg (3029 bytes) image13.jpg (2728 bytes) image14.jpg (2637 bytes)
B42 Series
The B42 service regulator incorporates a molded diaphragm and increased lever ratio into a conventionally designed regulator. The result is a lighter, more compact unit that provides the power, capacity, and relief performance of much larger regulators. Reduced weight means easier handling and installation. Reduced size means easier installation in limited spaces and a lower profile meter set. Typical applications include residential services, 2 psig systems, and small commercial services
B31 Series
The B31 service regulator is a high-performance regulator with a large effective diaphragm area and powerful lever ratio. The B31 is designed to maintain accurate regulation over a wide range of flows on systems with extreme variations in inlet pressure and to deliver high capacities with very low inlet pressures. Typical applications include demanding residential services and light commercial services.


B34S Series
The B34S service regulator is a compact, cost-effective regulator designed for midrange commercial applications. The B34S is particularly well-suited for quick on/off applications where shock problems can occur.

 

 

 



 

Previous Page

PAGE 5

Next Page

Page 1 / Page 2 / Page 3 / Page 4 / Page 5 / Page 6
Tech. Bulletins / HOME

[Brochures] [Products] [Hot Stuff] [Services] [Contact] [Related Links] [Tech Bulletins]

©2007 Power Equipment Company
2011 Williamsburg Road Richmond, VA 23231
804-236-3800 Fax 804-236-3882
sales@peconet.com
SITE MAP
Terms & Conditions