DUNGS
 |
per EN 88, Class A, Group 2 and DIN 3380, regulator group RG
10, zero shutoff, lock-up pressure group SG 30; safety diaphragm, internal
impulse line
ambient temperature: -15 to +70°C
max. inlet pressure: 500 mbar
outlet pressure range: 2.5 to 150 mbar
internal threads, Rp-ISO 7-1
flange connections, ISO 7005
FRS.../5 Pressure Regulator
FRNG.../5 Zero Pressure Regulator Proportionator (air pressure actuated)
outlet pressure range: 2.5 to 150 mbar
FR...503 to 520...Rp 3/8 to 2
FR...5040 to 5150...DN 40 to 150 |
 |
 |
FRSBV Safety Blow Off Valve
FRSBV 5100...Rp 1K0/1 Position Indicator;
indicates closed or open position of the safety valve. |
 |
 |
GW...A4 Pressure Switch
UB/NB...A4 High or Low Pressure LimitUB locks out and indicates when the
pressure exceeds set-point.
NB locks out and indicates when the pressure is below the set-point.
Double Pressure Switch
combination of two mechanically joined switches.
GW...A2, ...A5 Pressure Switches
to be used on double solenoid valves or MultiBlocs;
ambient temperature: -15 to +60°C
voltage: min. 10 to max. 250 VAC
min. 12 to max. 48 VDC
current AC: min. 20 mA to max. 5 A
DC:
min. 20 mA to max. 1 A
set-point ranges: 0.4 to 3 mbar, 1.0 to 10 mbar, 2.5 to 50 mbar, 30 to
150 mbar, 100 to 500 mbar. |
 |
 |
LGW...A1, LGW...C1
adjustable set-point via screw (requires manometer or equivalent to adjust)
LGW...A2, LGW...A4, LGW...C2
dial adjustable
LGW A2P 1/4" connection and test button
KS...C2 Klima-Set pressure switch with complete accessories for air
conditioning and ventilation systems. |
 |
Page 1 / Page 2
/ Page 3 / Page 4 /
Page 5
/ Page 6
Page 7 / Page 8 /
Page 9 / Page 10